CTH01 is a 12-channel LoRaWAN® power monitoring hub purpose-built for multi-circuit current monitoring, featuring non-invasive voltage measurement and industrial-grade analytics, helping commercial and industrial facilities cut costs and optimize efficiency.

  • 6 - 8 kHzSampling Frequency
  • 50 - 60 HzWorking Frequency
  • -20°C ~ 100°CMeasuring range

Specifications

CTH01 — Specifications
SpecificationValue
Electrical Measurement
Detection ParameterRMS Voltage and Current Power Factor Active, Reactive, Apparent Power Active (Imported or Exported), Reactive (Imported or Exported), Apparent Energy Voltage Three‑Phase Unbalance Voltage Total Harmonic Distortion (THDv) Current Total Harmonic Distortion (THDi)
Sampling Frequency6 - 8 kHz
Working Frequency50 - 60 Hz
AccuracyActive Energy: ±1% (according to IEC 62053-21) Reactive Energy: ±2% (according to IEC 62053-23)
Electrical Measurement — Temperature
Sensor TypeExternal NTC Sensor
Measuring range-20°C ~ 100°C
Measuring accuracy±1 %
Electrical Measurement — Voltage Interface
Circuit Configuration• Three-phase: phases L1 to L3 with or without Neutral • Single-phase: phases L with Neutral • Mixed Three-phase and Single-phase
Measuring Range100 - 500V AC
Measuring accuracy±1 %
Maximum Voltage (N-L)290 Vrms
Maximum Voltage (L-L)500 Vrms
Wire ConnectionAWG 26 - 12
Electrical Measurement — Current Interface
RangeUp to 1000A (Customizable Up to 4000 A)
Interface TypeRJ11
Port12 × Current Channels
Wireless Transmission
ProtocolLoRaWAN®
Antenna Connector1 × 50 Ω SMB - Female External Connector
FrequencyCN470/IN865/RU864/EU868/US915/AU915/KR920/AS923-1&2&3&4
Tx Power16 dBm (868 MHz)/20 dBm (915 MHz)/19 dBm (470 MHz)
Sensitivity-137dBm
ModeOTAA/ABP Class C
Others
LED Indicator1 × Status/Alarm Indicator
Button1 × Reset Button
USB1 × USB Type-C for Cable Temperature Sensor Connection
Software
ConfigurationMobile App via Bluetooth
Advanced FeatureData Storage (20,000 entries, 2,000 alarms), Data Analysis (12 months of energy statistics), Threshold Alarm, Out‑of‑Range alarm, Power Failure Alarm
Physical Characteristics
Power Supply12 V DC (±10 %)
Insulation Voltage4kVac(r.m.s)(1mA/1min)
Intrinsic ConsumptionMax. 5.8W
Pollution Degree2
Overvoltage CategoryⅢ
Maximum Altitude2000 m
Operating Temperature-20°C~70°C (-4°F~158°F)
Relative Humidity≤ 95% (Non-condensing)
Ingress ProtectionIP30
Housing&ColorABS+PC (UL94 V0), Starlight Grey
Dimensions49.3 × 98 × 90 mm (1.94 × 3.86 × 3.54 in)
Weight163g
InstallationDIN 35 Rail Mounting, Magnetic Mounting (Optional)
Approvals
RegulatoryETL Listed (UL/CSA 61010-1, UL/CSA 61010-2-030), CE (RED&LVD), FCC, SRRC
EnvironmentalRoHS

Interested in this product?

Request a quote: our team will confirm availability, compatibility and a deployment plan.

✉
WhatsAppCall usRequest a quote